Bunker Design 8 min read

LINAC & Radiotherapy Bunker Vault Shielding: Design Requirements

Technical guide to LINAC and radiotherapy bunker vault shielding — primary and secondary barriers, maze design, and megavoltage shielding requirements.

Megavoltage Shielding Is a Different Scale

A linear accelerator (LINAC) used for external beam radiotherapy operates at megavoltage energies — far higher than diagnostic X-ray or CT equipment. Where a diagnostic room might be shielded with lead-lined drywall or a lead-lined door, a LINAC vault typically requires walls of high-density concrete well over a metre thick, engineered as a purpose-built bunker rather than a fitted-out room.

Getting this shielding right is a structural engineering exercise as much as a radiation protection one, and it has to be resolved at the earliest planning stage — a LINAC vault cannot practically be retrofitted the way a lighter diagnostic room can.

Primary and Secondary Barriers

Bunker shielding design distinguishes between the primary barrier — the wall or ceiling directly in the path of the useful beam — and secondary barriers, which need to attenuate scattered and leakage radiation rather than the full primary beam.

Because the primary beam is so much more penetrating, primary barriers are substantially thicker than secondary barriers on the same vault. The gantry's range of rotation, the beam energy, and the workload (patient throughput) all feed into how thick each barrier needs to be.

Maze Design & Door Shielding

Most LINAC vaults use a maze entrance rather than a direct shielded door facing the treatment beam — the offset corridor allows scattered radiation to attenuate over distance and multiple reflections before reaching the entrance, meaning the door itself can be a lighter shielded door rather than requiring bunker-thickness material.

Maze length and configuration are calculated alongside the wall shielding, since a well-designed maze significantly reduces the shielding burden on the vault door — an important cost and practical consideration given how heavy a full primary-barrier-rated door would otherwise need to be.

  • ◆Primary barriers: engineered to attenuate the direct useful beam, typically concrete of significant thickness
  • ◆Secondary barriers: sized for scattered and leakage radiation, generally thinner than primary barriers
  • ◆Maze corridor: reduces scattered dose reaching the entrance, lightening the shielding needed at the door itself
  • ◆Shielded door: rated to the residual dose at the maze entrance rather than the full primary beam
  • ◆Penetrations: cable ducts, ventilation, and services routed to avoid direct line-of-sight radiation streaming

Design, Verification & Sign-Off

Bunker shielding calculations should be performed or verified by a qualified medical physicist working from the specific LINAC model, energy, and projected workload, with sign-off required from AEA Sri Lanka before the facility can be licensed to operate.